active power filter
Low voltage capacitor banks (TSC)
Oct 21, 2019

Introduction:

Based on DSP control technology and Instantaneous power control theory, Wanlida thyristor switched capacitor banks (TSC/TSF) with high-speed switching capability are designed to support the supply voltage of distribution systems and to correct the power factor and eliminate the harmonic current of connected loads.

Thyristor zero-crossing switching switches are resistant to mechanical wear, operate without noise, and are capable of practically transient-free switching, so it is more safety than contactor switched capacitor banks.


Functions:

1.Improve power factor

2.Stabilize busbar voltage and suppress subsynchronous resonance

3.Eliminate harmonic current

4.Decrease grid loss

5.Optimize reactive power

I6.ncrease transformer loading capacity


Principles:

Thyristor switched capacitor banks is the compensating device based on switching operation of capacitor banks by thyristor. TSC mainly consists of control system, thyristor, capacitors and reactors. Capacitor banks are divided into multiple units to realize step control. TSC is able to implement step regulating in reactive power, accuracy of regulating depends on numbers of multiple unit.

Thyristor switched capacitor banks (TSC/TSF) apply delta wiring. To optimize effect of reactive power compensating and harmonic filtering, TSC capacity and branch configuration must be designed according to reactive power variation and harmonic components from nonlinear load.


Technical features:

SN

Parameters

Value

1

Rated voltage

AC220V~1140V

2

Operation voltage

0.8~1.1Un

3

Rated frequency

50Hz/60Hz (Option)

4

Capacitor wiring mode

Delta/Star (Option)

5

Switching mode

Cycle/sequence/coded combination (Option)

6

Response time

<20ms

7

Allowable maximum over current

1.3 times of rated current

8

Control steps

1~12/1~16 (Option)

9

Multiple units operation mode

Parallel

10

Power loss

<0.5%

11

Communication modes

Modbus/RS485/232/CAN/GPRS etc (Option)

12

IP

IP40 (customized)

13

Cooling mode

Air cooling

14

Leading in mode

Bottom/Top/Busbar (Option)

15

Altitude

<1500 M

16

Ambient temperature

-200C~+500C

17

Ambient humidity

<95%

18

Operation environment

No condensation, no corrupt gas, no conductive dust, no explosive and inflammable materials

19

Installation requirement

No vibration, inclination≤50

20

Switching characteristic

Current zero-crossing switching

21

Harmonic display

Measure and display 2nd ~25th

22

Phase sequence protection

Fault phase, phase loss

23

Thyristor protection

Over-temperature protection and self-recovery

24

LCD display

Real time current and voltage

25

Emergency protection

Emergency stop switch

26

Compensation mode

Three-phase compensation, phase splitting compensation

27

Protection modes

Over current, over voltage, short-circuit, quick break